Voltage drop

The voltage drop is calculated from the current, the conductor length (circuit path plus wire reserve), the resistance and reactance of the conductors and the power factor, as a percentage of the circuit voltage. Parallel sets divide the impedance by the number of sets. A transformer adds its own drop to the three-phase circuits below it.

Formulas

  • Voltage drop of a circuit: VD = K × I × (R × cosφ + X × sinφ), in volts.
    • K is √3 for a three-phase circuit and 2 for a one- or two-pole circuit.
    • I is the design current of the circuit (see How a circuit is calculated).
    • R and X are the resistance and reactance of one conductor from the wire table (ohms per 1000 ft), multiplied by the conductor length and divided by the number of parallel sets.
    • cosφ is the power factor of the load.
  • In percent: EP_Voltage Drop = VD / U × 100 %, where U is the circuit voltage.
  • Total: EP_Total Voltage Drop = EP_Voltage Drop + total voltage drop at the panel that feeds the circuit. Each feeder passes its own total down to the panel it feeds.
  • Transformer: VD_T = √3 × I × (R_T × cosφ + X_T × sinφ) / U_LV, added to the total of every three-phase circuit below the transformer. I is the sum of the currents of the three-phase circuits it feeds, R_T and X_T come from its size and impedance, and U_LV is its secondary voltage.
LimitApplies toDefault
Branch circuit limitEP_Voltage Drop of branch circuits3 %
Feeder limitEP_Voltage Drop of feeders2 %
Total limitEP_Total Voltage Drop of branch circuits5 % (sum of both)

When a circuit reaches its limit, the conductor size steps up until the drop falls below it, and up to two more steps while the total drop exceeds the total limit. Limits come from the template of the project.