Breaker and conductor sizing
Breaker: every load is treated as continuous, so the breaker must be at least 125 % of the design current. Electric Pack picks the smallest rating of the breaker table that reaches it (the largest if none does). A rating you chose is kept while it is in the table and reaches the minimum.
Hot conductors: sized against the breaker rating — a size is accepted only when its corrected ampacity exceeds the rating. The table ampacity is multiplied by:
- the adjustment factor, from the number of hot and neutral conductors (the ground never counts);
- the temperature factor, from the ambient temperature and the temperature rating of the wire type.
One set is tried first; if the largest size is not enough, parallel sets are added, up to six.
Ground conductor: from the ground conductor table of the circuit. EP_GCS_Basis shows the rule used:
| EP_GCS_Basis | Meaning |
|---|---|
| Table | The size of the first rule of the ground conductor table at or above the breaker rating, for the conductor material of the wire family (copper or aluminum) |
| 250.122(B) | Only with Auto wire selection, the default NEC 250.122 table and AWG/kcmil sizes: the table size increased in proportion to the hot conductor area the voltage drop added (the final over the minimum total area, parallel sets included); EP_GCS_Ratio shows the factor |
| 250.122(A) | The increased size would be larger than the final hot conductor, so the ground conductor takes the hot conductor size |
| Same as Hot | The ground conductor table is set to follow the hot conductors, so the ground conductor takes the final hot conductor size |
| Custom | The Ground Conductors Size you set with Custom wire selection; without one, the table rules above apply |
A breaker rating above every rule of the ground conductor table gives no ground conductor size.
Your overrides: you can set the breaker table and rating, wire type, adjustment factor table, ambient temperature, wire reserve, parallel sets and conductor sizes. A hot conductor too small for the rating is replaced by the smallest size that fits, and a rating missing from the table is dropped.