Electrical Pack docs
Circuit breakers table
Open Settings > Circuit breakers and pick or create a table (see Working with settings tables).
| Column | What to enter | Example |
|---|---|---|
| Rating | A breaker rating in amperes | 70.00 (shown as 70.00 A) |
| Ampere Interrupting Capacity (AIC) | The interrupting capacity of that rating in kiloamperes | 7.5 (shown as 7.5 kA) |
- Each rating can appear only once in a table (This rating already exists).
- Electric Pack picks the smallest rating that is at least 125 % of the circuit current, so list every rating the manufacturer offers.
- The AIC is compared with the calculated fault current at the start of each circuit. A rating without AIC skips that check.

To make the table available on circuits, add it under Circuit Breakers of a template, or set it as Default Circuit Breaker (see Editing templates).