For every circuit Electric Pack selects the breaker and the conductors, calculates the voltage drop and the fault currents, and checks the results; for every panel it calculates the fault current at the bus. Revit provides the loads and currents from the devices; Electric Pack decides what the circuit needs.
Order of the calculation — from the top panels down, because each circuit depends on what feeds it:
- Read the tables of the circuit (breaker table, wire type, factors).
- Select the breaker.
- Select the hot conductors for the ampacity.
- Increase the size if the voltage drop requires it, and correct the ampacity.
- Size the ground conductor.
- Calculate the fault currents.
- Run the checks and collect the warnings.
Design current
| Poles | Current used for sizing |
|---|---|
| 1 | Total current of the circuit |
| 2 | Total current when both phases match, otherwise the larger phase |
| 3 | The largest of the three phases |
When it recalculates
| Trigger | What is recalculated |
|---|---|
| A change to a circuit, load or panel (moved, renamed, new distribution system) | Every circuit under the top feeder of each changed circuit, or under the top transformer feeding it |
| A change of the calculation settings | Every circuit of the model |
Only changed results are written, as a separate undo step Recalculate circuits. Undo and Redo start no recalculation.