Electrical Pack docs
Editing equipment and transformers
Select panels, switchboards or transformers (and no circuit). The panel shows:
| Value | Shown for | Input or result |
|---|---|---|
| X1/R1 Ratio | Transformers | Reactance to resistance ratio |
| Transformer Impedance Z1 | Transformers | Impedance, in the unit the hub sets (% or per unit) |
| Transformer Size | Transformers | kVA, for example 1000 |
| High Voltage Side / Low Voltage Side | Transformers | Primary and secondary voltage |
| Utility Fault at Primary | Transformers | kA, for example 25; taken from the feeder when it has a fault current |
| Equipment SCCR | Panels and switchboards | Short-circuit current rating, whole kA; empty = default 10 kA |
| Fault Current (Ik3) | Panels and switchboards | Result: fault current at the bus |


Equipment fed by no system shows a dash with Unable to calculate: no feeding system found for this equipment. The values of a virtual transformer are stored on the root panel it feeds.