Editing circuits in Properties

Open Properties: on the ElectricalPack tab, click Properties (the model must be connected to a hub project). Click again to hide it.

Edit a selection

  1. Select circuits in the model or in the System Browser. The top shows Elements selected: N.
  2. Pick or type a value.
  3. Move the focus out of the field.
image

The value is written to every selected circuit in one change. A field whose value differs between circuits shows <varies>. A value Electric Pack or Revit rejects is not stored, and the field shows the stored value again.

ValueInput or result
TypeSwitch between Branch Circuit and Feeder
Circuit Breaker TypePick a breaker table
RatingPick a rating of that breaker table
Protection Device AICResult: interrupting capacity of the breaker
Fault Current (Ik3 Start)Result: fault current at the start of the circuit
Fault Current (Ik3 End)Result: fault current at the end of the circuit
Wire TypePick a wire type
Wire SelectionAuto (Recommended) or a custom selection
Wire SizeResult: conductors of one set, with the number of parallel sets
Hot / Neutral / Ground Conductors SizePick sizes for a custom wire selection
Wire Reserve0, 3, 5 or 10 %, or any whole number from 0 to 99
Adjustment FactorPick an adjustment factor table
Number of RunsNumber of parallel sets (custom selection)
Ambient temperatureTemperature the conductors are derated for
Full Wire LengthResult: length the conductors are sized over, including the reserve
Total Connected LoadResult: connected load as a percentage of the rating
Wire Final AmpacityResult: ampacity after the factors
Voltage DropResult: voltage drop of the circuit, %
Total Voltage DropResult: voltage drop from the source to the end of a branch circuit, %

The group Revit parameters shows read-only values Revit states on the circuit: Length (All Devices), Apparent Load, Apparent Current, True Load, True Current, Power Factor, Voltage, Load Classification.

image

Note: Lowering the rating sets the conductors to the smallest sizes that rating allows, and the panel tells you so.

Auto and custom wire selection

Wire Selection decides who sizes the conductors of a circuit: Electric Pack (Auto, recommended) or you (Custom). In Custom, set Hot Conductors Size, Neutral Conductors Size, Ground Conductors Size and Number of Runs.

AutoCustom
Hot conductorsThe smallest size of the wire type whose ampacity reaches the breaker ratingThe Hot Conductors Size you set
Parallel setsAdded one at a time, up to 6, until the corrected ampacity exceeds the breaker ratingThe Number of Runs you set
Voltage dropThe size is raised until the voltage drop is within the limit of the circuit and, for a branch circuit, the total limitCalculated for your size only; the size is not raised, and a value over the limit shows a warning
NeutralThe final hot conductor sizeThe Neutral Conductors Size you set, while your hot size is kept
GroundFrom the ground conductor table or same as hotThe Ground Conductors Size you set; without one, from the ground conductor table

A custom size is never left too small for the breaker. When your hot size in your number of runs has a corrected ampacity that does not exceed the breaker rating, Electric Pack raises it to the smallest size that does, and the neutral follows the new size. Set Wire Selection back to Auto to let Electric Pack size the conductors again; the sizes you set are then ignored.

image

Breaker rating: Rating has no Auto mode. Electric Pack keeps the rating you pick while it reaches the minimum rating, 125 % of the circuit current (every load counts as continuous). A smaller rating is replaced by the smallest rating of the breaker table that reaches it.

Note: A circuit whose largest size of the wire type in 6 parallel sets still cannot carry the breaker rating shows an insufficient ampacity warning.

Can't find what you're looking for?
Send your request