Fault currents, AIC and SCCR

Electric Pack calculates the three-phase fault current at the start and end of every three-phase circuit and at the bus of every panel. The fault current at a point is the voltage of the nearest transformer above it, times the voltage factor, divided by the impedance from that transformer to the point. The impedance adds up from:

  • the utility, from the fault current at the transformer primary and the two transformer voltages (no data = infinite source, the conservative case);
  • the transformer, from its size, impedance and secondary voltage;
  • the conductors of every circuit in between, from their size, length and parallel sets.

The template standard sets the voltage factor: ANSI 1.0; IEC 1.1 with the impedance correction of IEC 60909. Circuits with one or two poles have no fault current, and none is calculated below a transformer with incomplete data.

Checks: the fault current at the start of a circuit is compared with the Protection Device AIC of its breaker, and the fault current at a bus with the Equipment SCCR of the panel (10 kA when none is set). Enter transformer data and SCCR in Properties.